The equipment for cleaning is shown in the cleaning system flow diagram . The pH of cleaning solutions used with elements can be in the range of 1–13 and therefore, non-corroding materials of construction should be used in the cleaning system.
Cleaning system flow diagram
Suggested Equipment
1.The mixing tank should be constructed of polypropylene or fiberglass-reinforced plastic (FRP). The tank should be provided with a removable cover and a temperature gauge. The cleaning procedure is more effective when performed at a warm temperature, and we recommend that the solution be maintained according to the pH and temperature guidelines listed in Table 6.1. We do not recommend using a cleaning temperature below 15°C because of the very slow chemical kinetics at low temperatures. In addition, chemicals such as sodium lauryl sulfate might precipitate at low temperatures. Cooling may also be required in certain geographic regions, so both heating/cooling requirements must be considered during the design. A rule of thumb in sizing a cleaning tank is to use the approximate volume of the empty pressure vessels and then add the volume of the feed and return hoses or pipes. For example, to clean ten 8-inch-diameter pressure vessels with six elements per vessel, the following calculations would apply:
=3.14(4 in) 2(20 ft)(7.48gal/ft 3 )/(144in 2 /ft2 )
V1=52 gal/vessael (0.2m 3 )
=3.14(1.91IN)2(50FT)(7.48GAL/FT 3 )/(144in 2 /ft 2 )
= 30 gals (0.11 m 3 )
Vct = V 10 + Vp = 520 + 30 = 550 gal.
Therefore, the cleaning tank should be about 550 gal (2.1 m3).
The cleaning pump should be sized for the flows and pressures given in Table 6.2, making allowances for pressure loss in the piping and across the cartridge filter. The pump should be constructed of 316 SS or nonmetallic composite polyesters.
Appropriate valves, flow meters and pressure gauges should be installed to adequately control the flow. Service lines may be either hard-piped or hoses. In either case, the flow rate should be a moderate 10 ft/s (3 m/s) or less.
Cleaning Elements In Situ
There are six steps in the cleaning of elements:
Table 1 pH range and temperature limits during cleaning
Element type | Max Temp 45°C (113°F) pH range | Max Temp 35°C( 95 °F) pH range | pH range Max Temp 25°C (77°F) pH range |
BW30, BW30LE, LE, XLE, TW30, TW30HP, NF90 | 1 – 10.5 | 1 – 12 | 1 – 13 |
SW30HR, SW30HR LE, SW30XLE, SW30 | 1 – 10.5 | 1 – 12 | 1 – 13 |
NF200, NF270 | 3 – 10 | 1 – 11 | 1 – 12 |
SR90 | 3 – 10 | 1 – 11 | 1 – 12 |
Table 6.2 Recommended feed flow rate per pressure vessel during high flow rate recycle
Feed pressure1
|
Element diameter
|
Feed flow rate per pressure vessel
|
||
psig
|
bar
|
inches
|
gpm
|
m3/h
|
20 – 60
|
1.5 – 4.0
|
2.5
|
3 – 5
|
0.7 – 1.2
|
20 – 60
|
1.5 – 4.0
|
4 2
|
8 – 10
|
1.8 – 2.3
|
20 – 60
|
1.5 – 4.0
|
6
|
16 – 20
|
3.6 – 4.5
|
20 – 60
|
1.5 – 4.0
|
8
|
30 – 40
|
6.0 – 9.1
|
20 – 60
|
1.5 – 4.0
|
8 3
|
35 – 45
|
8.0 – 10.2
|
Cleaning Tips
Acid cleaners typically react with silica, organics (for instance humic acids) and biofilm present on the membrane surface which may cause a further decline of the membrane performance. Sometimes, an alkaline cleaning may restore this decline that was caused by the acid cleaner, but often an extreme cleaning will be necessary. An extreme cleaning is carried out at pH and temperature conditions that are outside the membrane manufacturer’s guidelines or by using cleaning chemicals that are not compatible with the membrane elements. An extreme cleaning should only be carried out as a last resort as it can result in membrane damage.
If the RO system suffers from colloidal, organic fouling or biofouling in combination with calcium carbonate, then a two- step cleaning program will be needed: alkaline cleaning followed by an acid cleaning. The acid cleaning may be performed when the alkaline cleaning has effectively removed the organic fouling, colloidal fouling and biofouling.
In addition to applying the correct cleaning sequence (alkaline cleaning step first), selecting the correct pH is very critical for optimum foulant removal. If foulant is not successfully removed, the membrane system performance will decline faster as it is easier for the foulant to deposit on the membrane surface area. The time between cleanings will become shorter, resulting in shorter membrane element life and higher operating and maintenance costs.
Most effective cleaning allows longer system operating time between cleanings and results in the lowest operating costs.
Figure 1 and 2 below show the importance of the selecting the right pH for successful cleaning.
Figure 1. Effect of pH on the removal of calcium carbonate
Calcium carbonate is best removed by cleaning with hydrochloric acid at pH 1-2.
Figure 2. Effect of pH on the removal of biofouling
Cleaning Chemicals
Table 3 lists suitable cleaning chemicals. Acid cleaners and alkaline cleaners are the standard cleaning chemicals. The acid cleaners are used to remove inorganic precipitates including iron, while the alkaline cleaners are used to remove organic fouling including biological matter. Sulfuric acid should never used for cleaning because of the risk of calcium sulfate precipitation. Reverse osmosis permeate or deionized water should be used for the preparation of cleaning solutions.
Table 3. Simple cleaning solutions
Cleaner
Foulant |
0.1% (W) NaOH and pH 12, 35°Cmax. or 1.0% (W) Na4EDTA and pH 12, 35°C max.
|
0.1% (W) NaOH and pH 12, 35°C max. or 0.025% (W) Na-DSS and pH 12, 35°C max.
|
0.2% (W) HCI, 25°C and pH 1 – 2
|
1.0% (W) Na2S2O4, 25°C and pH 5
|
0.5% (W) H3PO4 , 25 °C and pH 1 – 2
|
1.0% (W) NH2SO3H , 25°C and pH 3 – 4
|
Inorganic Salts (for example, CaCO3) | Preferred | Alternative | Alternative | |||
Sulfate Scales (CaSO4, BaSO4) | OK | Preferred | Alternative | Alternative | ||
Inorganic Colloids (silt) | Preferred | |||||
Silica | Alternative | Preferred | ||||
Biofilms | Alternative | Preferred | ||||
Organic | Alternative | Preferred |
The temperatures and pH listed in table 3 are applicable for BW30, BW30LE, LE, XLE, TW30, TW30HP, SW30HR, SW30HR LE , SW30XLE, SW30 and NF90 membrane elements. For more information regarding the allowed temperatures and pH for cleaning, please refer to table 1.
Notes: